Catalogue Controller CDU-12 for Chemical Dosing Unit
|
|
|
|
|
Purpose and field of application | |
|
The CDU-12 controller is designed to operate as part of the
chemical dosing unit used for controlled injection of chemicals
into the annulus of oil wells, and into the oil gathering
pipeline.
|
|
CDU-12 Controller |
|
|
THE CONTROLLER PERFORMS THE FOLLOWING FUNCTIONS: | |
|
- control of the plunger pump drive for chemicals dosing in the manual and automatic mode;
- chemicals flow rate control;
- cyclic operation of the chemical dosing unit at the required flow rate;
- automatic restart of the unit in case of power supply failure;
- light indication of the unit operation modes: “STOP”, “STANDBY”, “IN OPERATION”;
- tank level control, including calculation of the volume and weight of the chemical;
- chemical’s temperature control in the tank;
- chemical’s heating control in the tank;
- control of pressure in the discharge line (contact pressure gauge or pressure sensor);
- electrohydraulic pusher motor protection (motor current and power voltage control);
- discharge line temperature control;
- control of discharge line heating;
- control of the production well switchboard status;
- control of the chemical dosing unit operation from the production well switchboard;
- indication of unauthorized access to the chemical dosing unit;
- reporting the unit status to the dispatch system;
- chemicals flow rate control via RS-485 interface;
- unit operation control via RS-485 interface;
- transmission of current parameters and the event log to the telemetry control system via RS-485 interface;
- event logging (65536 records with adjustable period);
- copying the event log to a standard USB stick via the USBHost interface;
- recording the number of plunger pump strokes;
- recording daily and total chemicals consumption since the start of the system operation;
- recording the operating time of the unit.
|
CONTROLLER’S SPECIFICATIONS | |
|
PARAMETER |
VALUE |
Rated supply voltage, V |
10 (50 Hz), 25 (50 Hz) |
Maximum voltage deviation from average , % |
-50... +50 |
Power consumption, W, max |
40 |
Ranges of controlled parameter variations and measurement errors
relative to the upper range limit: |
current, A |
0... 5 (±1.0%) |
voltage, V |
0... 380 (±1.0%) |
chemical temperature, °C
line temperature,°C |
-50... +150 (±1.0%) |
Ranges of analogue input variations and measurement errors relative to
the upper range limit: |
chemical level, mA
line pressure, mA |
4... 20 (±1.0%) |
Discrete inputs |
8 |
Relay outputs |
7 |
Switching capacity |
4 outputs |
Voltage, V, max |
250 |
Current, A, max |
6 |
3 outputs |
Voltage, V, max |
125 |
Current, A, max |
3 |
Interfaces |
RS-232, RS-485 (2 pcs.), USB-Host |
Weight, kg, max |
2.0 |
Overall dimensions, mm, max |
210x230x78 |
Climatic version |
UXL2 |
Enclosure type |
IP43, NEMA3, NEMA4 |
|
|
|
|
|
|
|
|
| |
RANGE of PRODUCTS
| |